The Pause button doesn't work when the measurement is running.

Zuletzt geändert 3rd Jan 2013
Category:  > DASYLab
Platform: All
Version: All
Article Ref.: 13C4E
»Zurück zur letzen Suche
»Print friendly version of this article.
1 person has found this article useful.
DASYLab 13C4E The Pause/Continue switch works only if the worksheet contains no hardware modules. The Pause function stops the acquisition of new data, for example, from the modules Generator, A/D Input, Digital Input, PID, or Slider. However, DASYLab continues processing the data acquired before the interruption until all data blocks have run through the worksheet to the data sink. If you have a hardware module in the worksheet and set the worksheet to Pause, the measurement board will continue to work, risking a buffer overflow. This is the reason why the Pause / Continue switch works only in simulation. DASYLab All All en DASYLab

Wenn Sie technische Fragen zu Soft- und Hardware haben, die bei uns erworben wurde, dann verwenden Sie dazu bitte unsere Knowledge Base. Falls Sie keine Antwort in unserer Knowledge Base finden, dann fllen Sie bitte hier das Formular fr Technischen Support aus oder rufen uns an unter +49 69 9675 9610 (werktags von 9 bis 13 Uhr).